Determination of modern reliability indicators of overhead power transmission lines of voltage classes 0.4-110 kV

https://doi.org/10.26897/2687-1149-2023-1-77-85

Abstract

   Reliability indicators for 0.4-110 kV overhead transmission lines need to be adjusted due to the lack of data on current values of reliability indicators for power system equipment. The authors’ analysis of official statistical data on the number of emergency and scheduled outages in the branches of PJSC “Rosseti Tsentr” and “Rosseti Tsentr i Privolzhye” revealed deviations of the reliability indicators of electrical equipment of power systems and power grids from those presented in RD34.20.574. Also, the analysis showed that the standard presented no values of average downtime for planned outages of 0.4 kV and 6-10 kV overhead power lines. Reliability values of 0.4-110 kV overhead power lines were determined. Failure rate of 0.4 kV overhead lines made 6.2 to 7.04 year-1/100·km, of 6-10 kV overhead lines – 5.27 to 8 year-1/100·km. The “Orelenergo” branch, a failure flow of 35 kV overhead lines was 0.57 year-1/100·km, and 110 kV overhead lines – 2.83 year-1/100·km. The calculated value of the average restoration time for 0.4 kV networks was 1.88 h; for 6-10 kV networks – 3.1 h; 35 kV – 6.8 h; 110 kV – 9.5 h. The estimated average number of intentional outages for 0.4 kV networks was 0.1 year-1; for 6-10 kV networks 0.72 year-1; for 35 kV networks 0.4 year-1; for 110 kV networks 0.51 year-1. The average idle time of 0.4 kV overhead lines and 6-10 kV overhead lines amounted to 13.6 hours and 10 hours, respectively. The calculated average downtime of 35 kV overhead lines and 110 kV overhead lines amounted to 24.7 hours and 37.6 hours, respectively. The received data specify modern reliability values of electric 0.4-110 kV networks that can be used when planning measures on developing networks and reconstructing them.

About the Authors

A. V. Vinogradov
Federal Scientific Agroengineering Center VIM; Russian State Agrarian University – Moscow Timiryazev Agricultural Academy
Russian Federation

Aleksandr V. Vinogradov, Associate Professor, Head of the Laboratory

Laboratory of Power Supply and Heat Supply

109428

Bld 5, 1st Institutskiy Proezd Str.

127550

49 Timiryazevskaya Str.

Moscow



A. A. Lansberg,
Federal Scientific Agroengineering Center VIM
Russian Federation

Aleksandr A. Lansberg, MSc student

109428

Bld 5, 1st Institutskiy Proezd Str.

Moscow



A. V. Vinogradova
Federal Scientific Agroengineering Center VIM
Russian Federation

Alina V. Vinogradova, CSc (Eng), Associate Professor

109428

Bld 5, 1st Institutskiy Proezd Str.

Moscow



References

1. Zakharov S., Kudryashov D., Brodt V., Pascar I., Voronin V. Analysis of accidents in 6-110 kV electric networks of Kuzbass power system. E3S Web of Conferences. 2018; 41: 03015. doi: 10.1051/e3sconf/20184103015

2. Konnov A. A. An analysis of the accident rate in 0.4 kV electrical networks of Nizhny Novgorod. Aktualnye nauchnye issledovaniya v sovremennom mire. 2020: 127-130. (In Rus.)

3. Khlebtsov A. P., Zaynutdinova L. Kh., Shilin A. N. Research into the current state of accident rate of electric networks in agriculture using the example of Astrakhan region. IOP Conference Series: Earth and Environmental Science. 2021; 723: 052015. doi: 10.1088/1755-1315/723/5/052015

4. Polkovskaya M., Yakupova M. Analysis of the causes of emergency shutdowns on electric networks. Journal of Physics: Conference Series. 2021; 2096: 012130. doi: 10.1088/1742-6596/2096/1/012130

5. Polkovskaya M., Buzina T., Fedurina N. Utilizing factor models to simulate emergency shutdowns of power grids. IOP Conference Series: Materials Science and Engineering. 2020; 939: 012059. doi: 10.1088/1757-899X/939/1/012059

6. Naumov I. V., Karpova E. V., Karamov D. N. Reliability level research in distribution electrical networks of Irkutsk. E3S Web of Conferences. 2019; 114: 03005. doi: 10.1051/e3sconf/201911403005

7. Kutsenko G. F., Puhalskaya O. Yu. Main reliability indicators of 6-10 kV transmission lines. Energetika. Izvestiya vysshih uchebnyh zavedenij i energeticheskih obedineniy SNG. 2006; 6: 20-23. (In Rus.)

8. Doronina O. I., Shevchenko N. Yu., Bakhtiarov K. N. Assessment of reliability of overhead power transmission lines taking into account climatic factors. Mezhdunarodniy zhurnal prikladnykh i fundamentalnykh issledovaniy. 2015; 9 (2): 226-230. (In Rus.)

9. Shatova Yu. A., Krivolapov A. A., Aleshina N. N. Reliability indicators of the power transmission line-220 kV of the Penza power system. Modern Problems of Science and Education. 2012; 6. URL: https://science-education.ru/ru/article/view?id=7864 (access date: 18. 06. 2022). (In Rus.)

10. Vinogradov A. V., Perkov R. A. Analysis of damage to electrical equipment of electrical networks and justifi cation of measures to improve the reliability of power supply to consumers. Vestnik NGIEI. 2015; 12 (55): 12-21. (In Rus.)

11. Lansberg A. A., Vinogradov A. V. Analysis of the length and types of wires used in 0.4-10 kV electric distribution networks of PJSC “Rosseti Tsentr and Privolzhye”. In: Molodezhnaya nauka – razvitiyu agropromyshlennogo kompleksa. Materialy II Vserossiyskoy (natsionalnoy) nauchno-prakticheskoy konferentsii studentov, aspirantov i molodyh uchenykh, Kursk. 2021; 351-355. (In Rus.)

12. Vinogradov A. V., Lansberg A. A., Sorokin N. S., Fomin I. N. Analysis of the technical condition and service life of rural electric networks of 6-10 kV in the Orel region. In: Professiya inzhener Sbornik statey X Vserossiyskoy molodezhnoy nauchno-prakticheskoy konferentsii “Professiya inzhener”, posvyashchyonnoy 40-letiyu fakulteta agrotekhniki i energoobespecheniya. A. L. Sevostyanov, E. V. Mishchenko, T. G. Pavlenko, I. V. Sidorova; ed. by. A. L. Sevostyanov; Orel State Agrarian University named after N. V. Parakhin. 2022; 482-486. (In Rus.)

13. Borodin M. V., Belikov R. P., Lansberg A. A. Analysis of the technical condition and capacity of the 110 kV overhead line of the branch of PJSC “MRSK Tsentr” Orelenergo. Vesti vysshikh uchebnykh zavedeniy Chernozemya. 2021; 1 (63): 40-50. (In Rus.)


Review

For citations:


Vinogradov A.V., Lansberg, A.A., Vinogradova A.V. Determination of modern reliability indicators of overhead power transmission lines of voltage classes 0.4-110 kV. Agricultural Engineering (Moscow). 2023;25(1):77-85. (In Russ.) https://doi.org/10.26897/2687-1149-2023-1-77-85

Views: 623


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 2687-1149 (Print)
ISSN 2687-1130 (Online)